beautypg.com

3 function chart "point level, 4 function chart, two-point control – VEGA VEGATOR 122 User Manual

Page 15

background image

15

6 Setup

VEGATOR 122 •

46108-EN-131217

Note:

Keep in mind that downstream connected devices are activated dur-

ing the function test. This allows you to check the correct function of

the measuring system.

6.3 Function chart "Point level"

The following chart provides an overview of the switching conditions

depending on the set mode and the level.
Note:

The switching conditions in the tables are only valid if the mode

switch on the sensor is set to "Max.".

Sensor

Signal conditioning instrument

Level

Sensor cur-

rent

LED yellow

(output)

LED red (fail-

ure)

Relay

approx. 8 mA

ON

approx. 16 mA

OFF

any

< 0.35 mA

> 6.8 mA

OFF

Sensor

Signal conditioning instrument

Level

Sensor cur-

rent

LED yellow

(output)

LED red (fail-

ure)

Relay

approx. 16 mA

ON

approx. 8 mA

OFF

any

< 3.6 mA

> 21 mA

OFF

6.4 Function chart, two-point control

The following charts provide an overview of the switching conditions

depending on the set mode and the level.

Overfill protection, point

level

Dry run protection, point

level