beautypg.com

2 mounting and connection, 2mounting and connection – VEGA Housing ISO-GEH.BXX for VEGAMET 381 User Manual

Page 3

background image

2

Mounting and connection

The housing is designed for wall/surface mounting and can be
fastened via four screws (max. ø 4 mm) after removal of the cover.
The hole distance is 160 x 110 mm.

If a signal conditioning instrument in Ex version is mounted, the housing
may not be installed in hazardous areas. Take note of the Ex-specific
safety instructions attached to each instrument with Ex approval.

1

Mount the instrument in the alloted place. The cable entries should
point downward to ensure better protection against moisture.

2

Snap the signal conditioning instrument onto the preassembled
carrier rail.

3

Carry out the wiring. Use cable with round cross-section. A cable
outer diamter of 7 … 12 mm ensures the seal effect of the cable
gland. If you are using cable with a different diameter or cross-
section, exchange the seal or use a suitable cable gland. Details
on mounting and electrical connection can be found in the
respecitive operating instructions manual.

4

Close unused cable gland openings with a stopper, or use blind
stoppers instead, so that the housing is sealed and the protection
rating maintained.

5

Insert the cover and tighten it with the white plastic screws.

Housing ISO-GEH.BXX • Protective housing for VEGAMET 381

3

2 Mounting and connection

38159

-

EN

-100604