11 Supplement
VEGAPULS 62 standpipe version • Foundation Fieldbus
36510-EN-121011
Fig. 32: Schematic presentation function block Output Splitter
Function block Signal Characterizer
The function block "Signal Characterizer" has two channels the outputs of which are not in linear
relation with the respective input. The non-linear relation is defined by a look-up table with individu-
ally selectable x/y-pairs. The respective input signal is imaged on the corresponding output, hence
this function block can be used in a control loop or signal path. Optionally the function axis can be
exchanged in channel 2 so that the block can be also used in a reverse control loop.
Fig. 33: Schematic presentation function block Signal Characterizer
Function block Integrator
The function block "Integrator" integrates a continuous input signal over the time and sums the
results of an impulse input block. It is used as a totalizer up to a reset or as a subtotalizer up to a
reference point at which the integrated and accumulated value is compared with the default values.
When these default values are reached, digital output signals will be outputted. The integration func-
tion is carried out upwardly starting with zero and downwards with a default value. Two flow values
are also available so that the net flow volume can be calculated and integrated. This can be used for
calculation of volume and mass changes in the vessel or for optimisation of flow controls.