Start your parameter adjustment with the following menu items of the
basic adjustment:
Proceed as follows:
1
Move from the measured value display to the main menu by
pushing [OK].
▶
Basic adjustment
Display
Diagnostics
Service
Info
2
Select the menu item "Basic adjustment" with [->] and confirm with
[OK]
. Now the menu item "Min. adjustment" is displayed.
Min. adjustment
0.00 %
=
10.000 m(d)
8.000 m(d)
3
Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
4
Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5
Save the settings with [OK] and move to "Max. adjustment" with [-
>
]
.
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1
Prepare the % value for editing with [OK] and set the cursor to the
requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.
2
Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3
Save the settings with [OK].
Carry out min. adjust-
ment
Carry out max. adjust-
ment
28
VEGAFLEX
66 • Profibus PA
6 Set up with the indicating and adjustment module PLICSCOM
34175
-EN
-100426