beautypg.com

VEGA VEGAPULS 67 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - two-wire User Manual

Page 64

background image

64

11 Supplement

VEGAPULS 67 • 4 … 20 mA/HART - two-wire

36531-EN-121011

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 200 mm (7.874 in)

Ʋ Reflector

Plane plate reflector

Ʋ False reflections

Largest false echo 20 dB smaller than the useful echo

Deviation with liquids

See following diagrams

10 mm (0.394 in)

- 10 mm (- 0.394 in)

2 mm (0.079 in)

- 2 mm (- 0.079 in)

0

1 2

3

1,0 m

(3.280 ft)

Fig. 53: Deviation under reference conditions
1 Reference plane

2 Antenna edge

3 Recommended measuring range

Reproducibility

≤ ±1 mm

Deviation with bulk solids

The values depend to a great extent on the application.

Binding specifications are thus not possible.

Deviation under EMC influence

≤ ±30 mm

Variables influencing measurement accuracy
Specifications apply to the HART signal and the current output
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm

Additional deviation through strong, high

frequency electromagnetic fields acc. to

EN 61326

< ±50 mm

Specifications apply also to the current output
Temperature drift - Current output

±0.03 %/10 K relating to the 16 mA span max. ±0.3 %

Deviation on the current output by ana-

logue/digital conversion

< ±15 µA

Deviation on the current output due to

strong, high frequency electromagnetic

fields acc. to EN 61326

< ±150 µA

Characteristics and performance data
Measuring frequency

K-band (26 GHz technology)

Measuring cycle time approx.

700 ms