beautypg.com

VEGA VEGABAR 55 4 … 20 mA_HART User Manual

Page 58

background image

58

10 Supplement

VEGABAR 55 • 4 … 20 mA/HART

36734-EN-130321

Ʋ 100 Hz … 10 kHz

U

ss

< 10 mV

Load

see diagram

1000

750

500

250

12

18

16

14

20

22

24

26

28

30

32

34

36

V

4

1

2

3

Fig. 29: Voltage diagram
1 HART load

2 Voltage limit Ex-ia instrument

3 Voltage limit non-Ex/Ex-d instrument

4 Operating voltage

Electrical protective measures
Protection rating

Ʋ Housing, standard

IP 66/IP 67

16)

Ʋ Aluminium and stainless housing

(optionally available)

IP 68 (1 bar)

17)

Ʋ Process component in IP 68 version IP 68 (25 bar)

Ʋ External housing

IP 65, IP 66/IP 68 (0.2 bar)

Overvoltage category

III

Protection class

II

Functional safety (SIL)
Functional safety is already activated on instruments with SIL qualification ex factory. On instru-

ments without SIL qualification ex factory, the functional safety must be activated by the user via

the display and adjustment module or via PACTware for applications according to SIL.

Functional safety according to IEC 61508-4

Ʋ Single channel architecture (1oo1D) up to SIL2

Ʋ double channel diversitary redundant

architecture (1oo2D)

up to SIL3

You can find detailed information in the supplied Safety Manual of the instrument series or under

"www.vega.com", "Downloads", "Approvals".
Approvals
Instruments with approvals can have different technical data depending on the version.

16)

Instruments with gauge pressure measuring ranges cannot detect the ambient pressure when submerged, e.g.

in water. This can lead to falsification of the measured value.

17)

Only with instruments with absolute pressure ranges.