VEGA VEGAPULS 65 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - four-wire User Manual
Page 56
56
11 Supplement
VEGAPULS 65 • 4 … 20 mA/HART - four-wire
36516-EN-121011
3
4
2
1
Fig. 39: Data of the input variable
1 Reference plane
2 Measured variable, max. measuring range
3 Antenna length
4 Useful measuring range
Max. measuring range
35 m (114.83 ft)
Recommended measuring range
up to 10 m (32.81 ft)
Output variable
Output signals
4 … 20 mA/HART - active; 4 … 20 mA/HART - passive
Terminal voltage passive
9 … 30 V DC
Shortcircuit protection
Available
Potential separation
Available
Signal resolution
0.3 µA
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current
22 mA
Starting current
≤ 3.6 mA
Load (4 … 20 mA/HART - active)
< 500 Ω
Damping (63 % of the input variable)
0 … 999 s, adjustable
HART output values
Ʋ PV (Primary Value)
Distance to the level
Ʋ SV (Secondary Value)
Level as percentage value
Ʋ TV (Third Value)
Linearised percentage value
Ʋ QV (Fourth Value)
Scaled measured value
Resolution, digital
< 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %