6 Set up with the indicating and adjustment module
VEGAPULS 68 • 4 … 20 mA/HART - two-wire
36535-EN-130205
Menu
Menu item
Default value
Display
Language
Like order
Displayed value
Distance
Display unit
m
Scaling size
Volume
l
Scaling
0.00 lin %, 0 l
100.00 lin %, 100 l
Backlight
Switched off
Additional adjust-
ments
Distance unit
m
Temperature unit °C
Probe length
Length of the standpipe Ex factory
Linearization
curve
Linear
HART mode
Standard
Address 0
6.4 Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If the instrument is equipped with an indicating and adjustment modu-
le, the data in the sensor can be saved in the indicating and adjust-
ment module. The procedure is described in the operating instructions
manual "Indicating and adjustment module" in the menu item "Copy
sensor data". The data remain there permanently even if the sensor
power supply fails.
The following data or settings for adjustment of the indicating and
adjustment module are saved:
•
All data of the menu "Setup" and "Display"
•
In the menu "Additional adjustments" the items "Sensor-specific
units, temperature unit and linearization"
•
The values of the user programmable linearization curve
The function can also be used to transfer settings from one instru-
ment to another instrument of the same type. If it is necessary to
exchange a sensor, the indicating and adjustment module is inserted
into the replacement instrument and the data are likewise written into
the sensor via the menu item "Copy sensor data".