VEGA VEGAFLEX series 60 Recurring function test User Manual
Page 16
Test 3.3 - Verification of the instrument parameters
□ Sensor documentation of the
setup available
or
□ Sensor documentation (at least 6
months old) is available
File name:
□ Parameters correspond
□ Parameters do not correspond -
however checked on correctness
File name:
□ Parameters do not correspond -
deviation not acceptable
File name:
□ Sensor documentation of the
setup not available
□ Parameters checked on correct-
ness and saved (recheck after 6
months necessary)
File name:
Test result
□ All parameters correct or
checked on correctness
□ Parameters not correct
Tester:
Test 3.4 - Verification of the echo data
Useful echo (completely on top)
□ Corresponds
□ Does not correspond
Corresponding amplitude
□ In the tolerance range
□ Not in the tolerance range
Test result
□ Corresponds
□ Does not correspond
Test 3.5 - Verification of the sensor reaction
Reduction of the level
□ Distance value [m] increases
□ Other reaction
Increase of the level
□ Distance value [m] decreases
□ Other reaction
Test result
□ Corresponding sensor reaction
□ Sensor reaction does not corre-
spond
●
Summary 92 % (λ
du
)
Date
Signature
Test 3.1 / 3.2 / 3.3 / 3.4 / 3.5
□ All five test points passed
□ One or several test points did not
pass
●
Summary 88 % (λ
du
)
Date
Signature
16
Recurring function test • for VEGAFLEX series 60
5 Test protocol - Recurring function test