4 connecting to power supply, 1 preparing the connection, 2 connection steps for version with housing – VEGA B62-30W User Manual
Page 12: 4connecting to power supply
4
Connecting to power supply
4
.1 Preparing the connection
Always keep in mind the following safety instructions:
l
Connect only in the complete absence of line voltage
Before starting setup make sure that the power supply corresponds to
the specifications on the type label.
For effective overvoltage protection, the cables between overvoltage
arrester and instrument should be as short as possible.
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.
4
.2 Connection steps for version with housing
Proceed as follows:
1
Loosen screws of the housing cover
2
Push the supply and connection cables through the cable gland
into the housing, strip approx. 1 cm (0.4 in) insulation from the
ends of the wires
3
Connect the wire ends according to chapter "Wiring plan" to the
terminals of the overvoltage arrester
4
Connect the outer ground terminal on the housing to potential
equalization
5
Check all cable connections, especially the ground connection, to
make sure they are tightened sufficiently
6
Tighten the compression nuts of the cable glands. The seal ring
must completely encircle the cable
7
Tighten screws of the housing cover
The electrical connection is finished.
Note safety instructions
Take note of sa-
fety instructions
for Ex applica-
tions
12
Overvoltage arrester • B62-30W
4 Connecting to power supply
40492
-EN
-110527