Technical data kfd2-sr2-ex2.2s, Configuration, Accessories – VEGA KFD2-SR2-Ex2.2S User Manual
Page 4
R
e
le
ase
da
te
20
10
-0
2-
02
18
:14
D
ate
of
i
ssue
20
10
-0
3-
19
18
12
84_
EN
G.
xml
Technical data
KFD2-SR2-Ex2.2S
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
4
Power feed modules KFD2-EB2...
The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 100 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical
contact uses the Power Rail to transmit collective error messages.
Power Rail UPR-03
The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.
The Power Rail must not be fed via the device terminals of the individual devices!
Configuration
7
8
9
10
11
12
1
2
3
4
5
6
13
14
15
1
2
PWR
CHK
OUT
S1
S2
S3
123
123
S1
S3
II
S2
I
Switch position
Operating status
Factory settings: switch 1, 2 and 3 in position I
S
Function
Position
1
Mode of operation
Channel I (relay)
energized
with high input current
I
with low input current
II
2
Mode of operation
Channel II (relay)
energized
with high input current
I
with low input current
II
3
Line fault detection
ON
I
OFF
II
Control circuit
Input signal
Initiator high impedance/
contact opened
low input current
Initiator low impedance/
contact closed
high input current
Lead breakage,
lead short-circuit
Line fault
Accessories