6 Set up with the display and adjustment module PLICSCOM

VEGABAR 52 • 4 … 20 mA/HART

36717-EN-130321

Basic adjustment

The "Reset" "Basic adjustment" resets the values of the following

menu items:

Menu section

Function

Reset value

Basic settings

Zero/Min. adjustment

Measuring range begin

Span/Max. adjustment

Measuring range end

Density

1 kg/l

Density unit

kg/l

Damping

1 s

Linearization

Linear

Sensor-TAG

Sensor

Display

Displayed value 1

bar

Displayed value 2

%

Display unit

Volume/l

Scaling

0.00 to 100.0

Decimal point indication 8888.8

Service

Current output - charac-

teristics

4 … 20 mA

Current output - failure

< 3.6 mA

Current output - min.

current

> 3.8 mA

Current output - max.

current

> 20.5 mA

The values of the following menu items are not reset with "Reset:

Menu section

Function

Reset value

Basic settings

Unit of measurement

No reset

Temperature unit

No reset

Position correction

No reset

Display

Backlight

No reset

Service

SIL

No reset

Language

No reset

HART mode

7)

No reset

Application

No reset

Peak value

The min. and max. temperature or pressure values are each reset to

the actual value.

Additional adjustment and diagnosis options such as e.g. scaling,

simulation or trend curve presentation are shown in the following

menu schematic. You will find a detailed description of these menu

Optional settings

7)

With instruments with signal output 4 … 20 mA/HART