VEGA VEGABAR 52 4 … 20 mA_HART User Manual
Page 37
37
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 52 • 4 … 20 mA/HART
36717-EN-130321
Basic adjustment
The "Reset" "Basic adjustment" resets the values of the following
menu items:
Menu section
Function
Reset value
Basic settings
Zero/Min. adjustment
Measuring range begin
Span/Max. adjustment
Measuring range end
Density
1 kg/l
Density unit
kg/l
Damping
1 s
Linearization
Linear
Sensor-TAG
Sensor
Display
Displayed value 1
bar
Displayed value 2
%
Display unit
Volume/l
Scaling
0.00 to 100.0
Decimal point indication 8888.8
Service
Current output - charac-
teristics
4 … 20 mA
Current output - failure
< 3.6 mA
Current output - min.
current
> 3.8 mA
Current output - max.
current
> 20.5 mA
The values of the following menu items are not reset with "Reset:
Menu section
Function
Reset value
Basic settings
Unit of measurement
No reset
Temperature unit
No reset
Position correction
No reset
Display
Backlight
No reset
Service
SIL
No reset
Language
No reset
HART mode
7)
No reset
Application
No reset
Peak value
The min. and max. temperature or pressure values are each reset to
the actual value.
Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve presentation are shown in the following
menu schematic. You will find a detailed description of these menu
Optional settings
7)
With instruments with signal output 4 … 20 mA/HART