To achieve a very precise switching point, you can install

VEGAVIB 55 horizontally. However, if the switching point can

have a tolerance of a few centimeters, we recommend

mounting VEGAVIB 55 approx. 20° inclined to the vessel

bottom to avoid buildup.

20°

a.

b.

Fig. 4: Horizontal mounting

a

Protective sheet

b

Concave protective sheet for abrasive solids

If VEGAVIB 55 is mounted in the filling stream, measurement

errors can result. Mount VEGAVIB 55 at a location in the

vessel where no disturbing influence from e.g. filling openings,

agitators, etc. can occur.

To minimise flow resistance caused by the tuning fork,

VEGAVIB 55 should be mounted in such a way that the

surfaces of the blades are parallel to the product movement.

Horizontal mounting

Inflowing medium

Flows

VEGAVIB 55 - - NAMUR