beautypg.com

9 supplement, 1 technical data – VEGA VEGALOG 571 EA User Manual

Page 19

background image

9 Supplement

9.1 Technical data

General data
Series

19" module card for BGT LOG 571

Dimensions

W = 25.4 mm (1 in), H = 128.4 mm (5.06 in), D

= 166 mm (6.54 in)

Weight

approx. 400 g (0.882 lbs)

Voltage supply
Operating voltage (PIN d2, z2)

24 V DC (18 … 36 V)

Power consumption

max. 11 W

Electrical connection
Module card

Multipoint connector according to DIN 41612,

series F, 48-pole (d, b, z) with coding hole

Module in carrier BGT LOG 571

Suitable female multipoint connector according

to DIN 41612 with connection via standard

connection technologies

Sensor input
Number of sensors

10x 0/4 … 20 mA

Kind of input (selectable)

2)

- Active input

Sensor power supply by VEGALOG 571 EA

- Passive input

sensors have an own power supply

Measured value transmission
- Analogue

0/4 … 20 mA

Terminal voltage
- Active circuit

approx. 24 V DC

Current limitation

approx. 26 mA

Linearity error

0.1 % of range (input active/passive)

Average lead error

0.5 % of range (input passive)

Temperature error

0.025 %/10 k of range

Connection cable

2-wire (screened) standard cable

2)

Selection is made separately for each input via the terminals

VEGALOG 571 EA - Input card analogue

19

Supplement

31948

-EN

-070307