sequence of the switching conditions must be monitored via

the switching amplifier as well as the connected systems. The

sensor must neither be removed nor response must be

triggered by filling the vessel. This applies to VEGAVIB 65 with

NAMUR oscillator VBE60N.
You can carry out the function test with the outputted current

values also directly with a safety PLC or a process control

system.

For measurement setups in conjunection with the NAMUR

oscillator VBE60N, a function test can be carried out. The

integration time must be set to 0.5 s. VEGAVIB 65 has an

integrated simulation key. The simulation key is lowered on the

oscillator. Push the simulation key for >2 seconds.
If VEGAVIB 65 is connected to an SPLC, you have to interrupt

the connection cable to the sensor for >2 seconds.
After releasing the simulation key or briefly interrupting the

connection cable to the sensor, you can check the complete

measuring system on correct function. A switching procedure

is simulated during the test.

2,2

I/mA

1

3

4,5

t/s

1

2

Fig. 14: Flow chart of the function test

1

Full signal

2

Empty signal

Check if the switching conditions occur in the correct

sequence and the stated time period. If this is not the case,

there is a fault in the measuring system. Keep in mind that

connected instruments are activated during the function test.

By doing this, you can check the correct function of the

measuring system.

(after releasing the simulation key)

Simulation key on the elec-

tronics module

Test procedure

22

VEGAVIB 65 - with NAMUR output

Set up

31218

-EN
-060508