VEGA VEGAFLEX 63 4 … 20 mA_HART four-wire User Manual
Page 25

2
E
nter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.
3
S
ave the settings with [OK].
E
ach product has different reflective properties. In addition, there are
various interfering factors which have to be taken into account:
agitated product surfaces and foam generation (with liquids); dust
generation, material cones and echoes from the vessel wall (with
solids). To adapt the sensor to these different conditions, you should
fi
rst select in this menu item under "Medium" either "Liquid" or "Solid".
A
pplication
Liquid
Standard
(DK ≥ 2)
D
epending on the dielectric figure (dielectri value or ε
r
),
measured
products can have a different reflective property. Therefore an
additional selection possibility is available.
U
nder "Sensitivity" you can select "Standard (DK ≥ 2)" or "Increased
sensitivity (DK < 2)".
T
hrough this the sensor is optimally adapted to the product and
measurement reliability, particularly in products with bad reflective
properties, is considerably increased.
E
nter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
T
o suppress fluctuations in the measured value display, e. g. caused
by an agitated product surface, a damping can be set. This time can
be between 0 and 999 seconds. Keep in mind that the reaction time of
the entire measurement will then be longer and the sensor will react to
measured value changes with a delay. In general, a period of a few
seconds is sufficient to smooth the measured value display.
D
amping
0
s
E
nter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
A
linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. in a horizontal cylindrical
or spherical tank - and the indication or output of the volume is
required. Corresponding linearization curves are preprogrammed for
Application
Damping
Linearisation curve
VEGAFLEX
63 • 4 … 20
mA/HART four-wire
25