6 Setup

VEGACAP 69 • - Relay (DPDT)

31175-EN-130916

7. Reset meas. range selection switch (2) to the next lower range in

which the control lamp lights green [lights red].

8. Fill the vessel until the probe is completely covered.
9. Turn the potentiometer (1) very slowly clockwise until the control

lamp lights green [lights red].

10. Note the position of the potentiometer (1). We recommend docu-

menting the value of the empty switch point and the full switch

point as well as the range.

11. If the control lamp does not light green [light red], then you have

to set the meas. range switch (2) to the next higher stage and

repeat the setting with the potentiometer until the control lamp

lights green [lights red].

12. Set the potentiometer (1) to the average value of the two noted

values.

The measuring system is now ready for operation.

Empty adjustment

Full adjustment

range 1
range 2
range 3

Tab. 1: Note the position of the potentiometer.

Note:

If you do not find the full switch point in one of the ranges, we recom-

mend setting the meas. range selection switch (2) to the lowest range

in which you have found the empty switch point. Set the potentiometer

(1) to the average value between empty switch point and 10.
Vertically mounted probes

1. Set mode switch (3) to mode max.
2. Set meas. range selection switch (2) to range 1.
3. Fill the vessel up to the requested level.
4. Turn potentiometer (1) to position 10.

When the control lamp (6) lights red: set the measuring range

selection switch (2) to the next higher measuring range.
When the control lamp (6) lights green: continue with the next

item.

5. Turn the potentiometer (1) very slowly anticlockwise until the

control lamp (6) lights red.

The measuring system is now ready for operation.
1. Set mode switch (3) to mode min.
2. Set meas. range selection switch (2) to range 1.
3. Lower the level to the requested min. level.
4. Turn the potentiometer (1) to 0, the control lamp (6) lights green.
5. Turn the potentiometer (1) very slowly clockwise until the control

lamp (6) lights red. If the control lamp does not light red, set the

meas. range selection switch (2) to the next higher stage and

Mode max. (max. level

detection)

Mode min. (min. level

detection)