beautypg.com

VEGA VEGAWAVE 62 - Relay (DPDT) User Manual

Page 12

background image

d

d

6

1

2

3

Fig. 4: Filling in the centre, emptying laterally

1

VEGAWAVE 62

2

Discharge opening

3

Filling opening

The vibrating element should protrude into the vessel to avoid buildup.
For that reason, avoid using mounting bosses for flanges and screwed
fittings. This applies particularly to use with adhesive products.

If VEGAWAVE 62 is mounted in the filling stream, unwanted false
measurement signals can be generated. For this reason, mount
VEGAWAVE

62 at a position in the vessel where no disturbances, e.g.

from filling openings, agitators, etc., can occur.

Socket

Inflowing medium

12

VEGAWAVE

62 • - Relay (DPDT)

4 Mounting

32252

-EN

-120418