6
Set up
6
.1 General information
The figures in brackets refer to the following illustrations.
On the electronics module you will find the following indicating and
adjustment elements:
l
Potentiometer for adaptation to the product density (1)
l
DIL switch for mode adjustment - min./max. (2)
l
Simulation key (3)
l
Signal lamp (6)
6
.2 Adjustment elements
4
5
6
3
1
2
Simulation
NAMUR IEC 60947-5-6
VB60N
Fig. 12: Electronics and connection compartment - NAMUR output
1
Potentiometer for switching point adaptation
2
DIL switch for characteristics reversal
3
Simulation key
4
Ground terminal
5
Connection terminals
6
Control lamp
With the potentiometer you can adapt the switching point to the solid. It
is already preset and must only be modified in special cases.
As a default setting, the potentiometer of VEGAVIB 63 is set to the
complete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light solids
you have to turn the potentiometer to the complete left position
(0.02 … 0.1 g/cm³ or 0.0007 … 0.0036 lbs/in³). By doing this,
Function/Configuration
Electronics and connec-
tion compartment
Switching point adapta-
tion (1)