6 Setup

VEGASWING 63 • - transistor (NPN/PNP)

29230-EN-130409

6 Setup

6.1 General information

The figures in brackets refer to the following illustrations.

With plastic housings, the switching condition of the electronics can

be checked when the housing cover is closed (control lamp). With the

basic setting, products with a density > 0.7 g/cm³ (0.025 lbs/in³) can

be detected. For products with lower density, the switch must be set

to > 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following indicating and

adjustment elements:

Signal lamp (1)

DIL switch for mode adjustment - A/B (2)

DIL switch for sensitivity adjustment (3)

Note:

For test purposes, immerse the tuning fork of VEGASWING 63 always

in liquids. Do not test the function of VEGASWING 63 with your hand.

This can damage the sensor.

6.2 Adjustment elements

1

2

3

4

1
2
3

Fig. 15: Oscillator SWE60T - Transistor output
1 Signal lamp (LED)

2 DIL switch for mode adjustment

3 DIL switch for sensitivity adjustment

Control lamp for indication of the switching status

Green = Output closed

Red = Output open

red (flashing) = failure

With the mode adjustment (A/B) you can change the switching

condition of the relay. You can set the required mode according to the

Function/Configuration

Signal lamp (1)

Mode adjustment (2)