beautypg.com

3 continuous level measurement – VEGA VEGACAL 66 For connection to a signal conditioning instrument User Manual

Page 20

background image

20

6 Setup with a signal conditioning instrument

VEGACAL 66 • For connection to a signal conditioning instrument

30321-EN-130917

6.3 Continuous level measurement

Continuous measurement requires a constant dielectric value, i.e. the

measured product should have constant properties.
Select the stage with the measuring range selection switch on the

electronics module of the probe according to the following chart.
Look in the row that corresponds to your product and select an ap-

propriate range according to the length of your probe.
The listed lengths do not completely correspond to those of the

actually available measuring probes. If the product has a dielectric

constant that lies between the values stated in the chart, the max.

permissible probe length for each range must be calculated accord-

ingly. For longer lengths or if there is no information available in the

chart, select range 3. If you are not sure, always set the measuring

range selection switch to the next higher stage.

VEGACAL 66

non-conductive and dielectric con-

stant = 2

range 3

non-conductive and dielectric con-

stant = 10

range 3

conductive or dielectric constant > 50 0 - 0.4 m = range 1 / 0.4 - 2.2 m =

range 2

Tab. 1: Range setting

Tip:

For min. adjustment the vessel should be as empty as possible, and

for max. adjustment, as full as possible. If the vessel is already full,

start with max. adjustment.
1. Set range changeover switch on the capacitive probe according

to the above chart

2. Carry out the adjustment on the signal conditioning instrument

(see operating instructions manual of the signal conditioning

instrument: "Adjustment with medium")

If error E014 is outputted on the signal conditioning instrument, you

will find information in the operating instructions manual of the signal

conditioning instrument under„Error codes“. If the sensor and supply

cable are working properly, it may be that an incorrect range has been

set for the capacitive probe. Set the measuring range selection switch

to the next higher stage.
If error E017 is outputted on the signal conditioning instrument, set

the measuring range selection switch on the probe one step lower.
1. Set range changeover switch on the capacitive probe according

to the above chart

2. Carry out the adjustment on the signal conditioning instrument

(see operating instructions manual of the signal conditioning

instrument: "Adjustment with medium")
When connecting to an analogue input card of a PLC, take note

of the operating instructions manual of the input card. The vessel

General information

VEGAMET series 500

signal conditioning

instrument

VEGAMET series 600

signal conditioning

instrument

Analogue input card of

a PLC