VEGA VEGACAL 63 Foundation Fieldbus User Manual
Page 40
40
10 Supplement
VEGACAL 63 • Foundation Fieldbus
30029-EN-130917
Ʋ Flange version ≥ 3"/DN 80, plated
-0.4 … 64 bar/-40 … 6400 kPa (-5.8 … 928 psig), de-
pending on the process fitting
Process temperature VEGACAL 63 of 316L
Ʋ Insulation PE
-40 … +80 °C (-40 … +176 °F)
Ʋ Insulation PTFE
-50 … +150 °C (-58 … +302 °F)
Process temperature (thread or flange
temperature) with temperature adapter
(option with PTFE)
-50 … +200 °C (-58 … +392 °F)
1
2
3
-50°C
(-58°F)
50°C
(122°F)
40°C
(104°F)
-40°C
(-40°F)
80°C
(176°F)
0°C
(32°F)
100°C
(212°F)
150°C
(302°F)
200°C
(392°F)
Fig. 24: Ambient temperature - Process temperature
1 Process temperature
2 Ambient temperature
3 Temperature range with temperature adapter
Dielectric constant
≥ 1.5
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Cable entry/plug
2)
Ʋ Single chamber housing
– 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5
or:
– 1 x closing cap M20 x 1.5; 1 x blind plug M20 x 1.5
or:
– 1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
– 1␣x plug (depending on the version), 1␣x blind stopper
M20␣x␣1.5
2)
Depending on the version M12 x 1, according to DIN 43650, Harting, 7/8" FF.