VEGA VEGASON 64 4 … 20 mA_HART four-wire User Manual
Page 34
E
nter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
A
part from the medium, the vessel shape can also influence the
measurement. To adapt the sensor to these measuring conditions, this
menu item offers different options depending on whether liquid or solid
is selected. With "Liquids" these are "Storage tank", "Stilling tube",
"
Open vessel" or "Stirred vessel", with "Solid", "Silo" or "Bunker".
V
essel form
Storage tank
E
nter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
T
o suppress fluctuations in the measured value display, e. g. caused
by an agitated product surface, a damping can be set. This time can
be between 0 and 999 seconds. Keep in mind that the reaction time of
the entire measurement will then be longer and the sensor will react to
measured value changes with a delay. In general, a period of a few
seconds is sufficient to smooth the measured value display.
D
amping
0 s
E
nter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
A
linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e. g. with a cylindrical or
spherical tank - and the indication or output of the volume is required.
C
orresponding linearization curves are preprogrammed for these
vessels. They represent the correlation between the level percentage
and vessel volume. By activating the appropriate curve, the volume
percentage of the vessel is displayed correctly. If the volume should
not be displayed in percent but e.g. in l or kg, a scaling can be also set
in the menu item "Display".
L
inearisation curve
linear
E
nter the requested parameter via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
Vessel form
Damping
Linearisation curve
34
VEGASON
64 • 4 … 20
mA/HART four-wire
6 S
et up with the indicating and adjustment module PLICSCOM
28781
-EN