VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) Profibus PA User Manual
Page 50
Error
Cause
Removal
In Simatic S7 the
measured value is
always presented
as 0
Only four bytes
are consistently
loaded in the PLC
Use function component SFC 14 to
load 5 bytes consistently
Measured value
on the indicating
and adjustment
module does not
correspond to the
value in the PLC
The menu item
"
Display - Dis-
play value
"
is
not set to "
PA-
Out
"
Check values and correct, if neces-
sary
No connection
between PLC and
PA network
Incorrect adjust-
ment of the bus
parameter and
the segment
coupler-depen-
dent baud rate
Check data and correct, if necessary
Instrument does
not appear during
connection setup
Profibus DP cab-
le pole-reversed
Check cable and correct, if necessary
Incorrect termina-
tion
Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification
Instrument not
connected to the
segment, double
assignment of an
address
Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E
013
l
no measured value available
à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or
wrong parameter adjustment
?
E
017
l
Adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E
036
l
no operable sensor software
à Carry out a software update or send instrument for repair
Fault messages via the
indicating/adjustment
module
50
VEGAPULS
61 • Profibus PA
8 Maintenance and fault rectification
28444
-EN
-100426