As a default setting, the potentiometer of VEGAVIB 61 is set to the
complete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light solids
you have to turn the potentiometer to the complete left position
(0.02 … 0.1 g/cm³ or 0.0007 … 0.0036 lbs/in³). By doing this,
VEGAVIB
61 will be more sensitive and light solids can be detected
more reliably.
For instruments detecting solids in water, these settings are not
applicable. The switching point adaptation is preset and must not be
changed.
With the mode switch (min./max.) you can change the switching status
of the transistor output. You can set the required mode according to
the "Function chart" (max. - max. detection or overflow protection, min.
- min. detection or dry run protection).
We recommend connecting according to the quiescent current
principle (switching output is opened when the switching point is
reached) because the transistor output takes on the same (safe)
condition if a failure is detected.
Control lamp for indication of the switching status
l
Green = Output closed
l
Red = Output open
l
red (flashing) = failure
6
.3 Function chart
The following chart provides an overview of the switching conditions
depending on the adjusted mode and level.
Level
Switching status Control lamp
Mode max.
Overflow protec-
tion
closed
Green
Mode max.
Overflow protec-
tion
open
Red
Mode min.
Dry run protection
closed
Green
Mode adjustment (2)
Signal lamp (5)
VEGAVIB
61 • - transistor (NPN/PNP)