E017
l
Adjustment span too small
à
Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
?
E036
l
no operable sensor software
à
Carry out software update or send instrument for repair
?
E041
l
Hardware error, electronics defective
à
Exchange instrument or return instrument for repair
?
E113
l
Communication conflict
à
Exchange instrument or return instrument for repair
8.3 Exchange the electronics module
If the electronics module is defective, it can be replaced by the
user.
In Ex applications, only an instrument and an electronics
module with appropriate Ex approval may be used.
If there is no electronics module available on site, one can be
ordered from the VEGA agency serving you.
The order data of the sensor must be downloaded into the new
electronics module. This can be done:
l
at the factory by VEGA
l
or on site by the user
In both cases, the sensor serial number is necessary. The
serial numbers are stated on the type label of the instrument or
on the delivery note.
Sensor serial number
Maintenance and fault rectification
VEGASON 66 - Profibus PA
43