VEGA VEGACAL 64 Foundation Fieldbus User Manual
Page 34
34
8 Maintenance and fault rectification
VEGACAL 64 • Foundation Fieldbus
30032-EN-130917
Error
Cause
Rectification
Measured val-
ue on the display
and adjustment
module does not
correspond to the
value in the PLC
The menu item
"Display - Display
value" is not set to
"PA-Out"
Check values and correct, if neces-
sary
No connection be-
tween PLC and
PA network
Incorrect adjust-
ment of the bus
parameter and the
segment coupler-
dependent baud
rate
Check data and correct, if necessary
Instrument does
not appear during
connection setup
Profibus DP cable
pole-reversed
Check cable and correct, if necessary
Incorrect termi-
nation
Check termination at the beginning
and end points of the bus and termi-
nate, if necessary, according to the
specification
Instrument not
connected to the
segment, double
assignment of an
address
Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
Error
Cause
Rectification
E013
no measured val-
ue available
– Probe insulation damaged, short-
circuit due to permeating, conduc-
tive medium
– Exchange the instrument or send it
in for repair
Shortcircuit in the
probe, e.g. be-
cause of moisture
in the housing
– Remove the electronics module out
of the probe and check the resistor
between the two marked plug con-
nections according to the figure in
paragraph "Check the resistance in
the probe".
– There should be no contact
between any of the connections
(high resistance)
– If there is still a connection -
exchange the instrument or return
it for repair
E017
Adjustment span
too small
Carry out a fresh adjustment and in-
crease the distance between min. and
max. adjustment
E036
no operable sen-
sor software
Carry out a software update or send
instrument for repair
E113
Communication
conflict
Exchange the instrument or send it in
for repair
Error messages via the
display and adjustment
module