beautypg.com

2 dimensions, Vegacap 66, housing – VEGA VEGACAP 66 - contactless electronic switch User Manual

Page 30

background image

30

9 Supplement

VEGACAP 66 • - contactless electronic switch

30021-EN-130916

DIL switch for measuring range selection

Ʋ range 1

0 … 20 pF

Ʋ range 2

0 … 85 pF

Ʋ range 3

0 … 450 pF

Potentiometer

Switching point adaptation

Voltage supply
Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 253 V DC

Domestic current requirement

approximately 3 mA (via load circuit)

Load current

Ʋ Min.

10 mA

Ʋ Max.

400 mA (at I > 300 mA the ambient temperature can be

max. 60 °C/140 °F) max. 4 A up to 40 ms

Electrical protective measures
Protection rating

IP 66/IP 67

Overvoltage category

III

Protection class

I

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

9.2 Dimensions

VEGACAP 66, housing

3

2

1

4

~ 69 mm

(2.72")

ø 79 mm

(3.11")

117 mm (4.61"

)

M20x1,5/

½ NPT

~ 59 mm

(2.32")

ø 80 mm

(3.15")

112 mm (4.41"

)

M20x1,5/

½ NPT

~ 69 mm

(2.72")

ø 79 mm

(3.03")

112 mm (4.41"

)

M20x1,5/

½ NPT

~ 116 mm (4.57")

ø 86 mm (3.39")

11

6 mm (4.57"

)

M20x1,5

M20x1,5/

½ NPT

Fig. 33: Housing versions
1 Plastic housing

2 Stainless steel housing, electropolished

3 Stainless steel housing, precision casting

4 Aluminium housing