VEGA VEGAPULS 43 Profibus PA User Manual
Page 49
VEGAPULS 43 – Profibus PA
49
Technical data
Characteristics
1)
(typical values under reference conditions, all statements relate to the nominal measuring
range)
Min. span between
full and empty
> 10 mm (recommended > 50 mm)
Frequency
26 GHz
Intervals
- two-wire sensor
0.6 s
- four-wire sensor
0.5 s
Beam angle (at -3 dB)
- DN 50, ANSI 2“
15°
- DN 80, ANSI 3“
10°
- DN 100, ANSI 4“
10°
- DN 150, ANSI 6“
10°
- Clamp 2“
15°
- Clamp 3“
10°
- Clamp 4“
10°
Adjustment time (response time)
2)
> 1 s (depending on parameter setting)
Influence of the process temperature
at 0 bar not measurable;
at 5 bar 0.004 %/10 °K;
at 40 bar 0.03 %/10 °K
Influence of the process pressure
0.0265 %/bar
Emitted radar power (average)
0.717 µW
Received average emitted power
3)
- distance 1 m
0.4 … 3.2 nW per cm² (0.4 … 3.2 x 10
-9
W/cm²)
- distance 5 m
0.02 … 0.13 nW per cm²
Ambient conditions
Vessel pressure
-100 … 1600 kPa (-1 … 16 bar)
Ambient temperature on the housing
- 4 … 20 mA two-wire sensor
-40°C … +80°C
- 4 … 20 mA four-wire sensor
-40°C … +80°C
- 4 … 20 mA four-wire sensor Ex d ia
-40°C … +60°C
Process temperature (flange temp.)
-40°C … +150°C
Storage and transport temperature
-60°C … +80°C
Protection
IP 66 and IP 67
Protection class
- two-wire sensor
II
- four-wire sensor
I
Overvoltage category
III
1)
Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g.
temperature 15 °C … 35 °C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar
2)
The adjustment time (also actuating time, response time or adjustment period) is the time required by the
sensor to output the correct level (with max. 10% deviation) after a sudden level change.
3)
Average emitted power (electromagnetic energy) received by a body per cm² directly in front of the antenna.
The received emitted power depends on the antenna version and the distance.