VEGAFLEX 54K

23

Setup

Adjust-
ment

Para-
meter
adjust-
ment

Sensor

m(d)

4.700

w.o.
medium

Ad-
just-
ment
in

m(d)

0.0 %

at

m (d)

XX.XXX

(min. adjustment)

OK

OK

OK

OK

with
medium

Min.
adjust
at %

XXX.X

Max.
adjust
at %

XXX.X

1)

1. Adjustment

Under the menu item "

Adjustment", you inform

the sensor of the measuring range it should
operate in.
The instruments are already adjusted to the
respective probe length. You only have to
carry out a max. adjustment and enter the
max. level.

1)

In case of two values which can be modified, you
can move with the "+" key to the second value
(confirm with the "OK" key).

Adjustment with medium

Fill the vessel e.g. to 10 %, enter in the menu
"

Min-adjustment" with the "+" and "–" keys

10 % and confirm with the "OK" key. Then fill
the vessel e.g. to 80 % or 100 %, enter in the
menu "

Max-adjustment" with the "+" and "–"

keys 80 % or 100 % and confirm with the
"OK" key.

You can carry out the adjustment with or
without medium. Generally, you will carry out
the adjustment without medium, because you
can adjust without having to fill the vessel.

Adjustment without medium

• Enter the distance of your sensor to the

medium at 0 % (example: 5.850 m) with the
"

+" and "–" key.

If you do not know the distance, you have
to do a sounding.

• Enter the distance from the sensor to the

medium at 100 % filling.

Max.

Min.

100 % (distance to the product
0.300 m) corresponds to

1200 liters, e.g. 20 mA

Meas. range

0 % (distance to the product
5.850 m) corresponds to 456
liters, e.g. 4 mA)

Key

Display indication