beautypg.com

VEGA D84 Ball valve fitting User Manual

Page 6

background image

6

Ball valve fitting

Mounting

2 Mounting the pressure transmitter in a filled vessel

Safety information:

When mounting the pressure transmitter, the pressure in the vessel can be max. 2 bar
(200 kPa)

• Starting point: Vessel is filled, ball valve is

closed.

• Open the ventilation valve

• Insert the pressure

transmitter into the
opening of the ball
valve fitting.

• Lead the two safety pins through

the flange of the pressure transmit-
ter and secure each of the two
safety pins with two U-washers, two
O-rings and a self-locking hexagon
nut M8-DIN985. Locate the parts as
shown in the illustration.
Be aware that self-locking nuts will
loose their safety effect after being
mounted and dismounted several
times.