Electrical connection
3.2 Connection of the sensor
• Loosen the closing screw on the upper
side of the sensor.
• Open the sensor cover.
• Remove the sleeve nut of the PG and shift
the nut slightly over the connection cable.
• Remove the rubber seal from the PG and
shift the seal over the connection cable.
• Remove the outer insulation of the connec-
tion cable over a length of approx. 10 cm.
• Insert the cable through the PG into the
sensor.
• Connect the cables. Push the white tabs of
the spring terminals with a small screw-
driver and insert the copper core of the
connection cable into the terminal opening.
Check the hold of the individual wires in the
terminals by pulling lightly on them.
• Screw the sleeve nut back onto the PG and
screw it down tightly.
Two-wire technology (analogue)
(loop powered)
Four-wire technology
(separate supply)
OK
-
+
ESC
-
+
Display
5
6
7
8
Communication
2 -
4-20mA
+ 1
2.23272
OK
-
+
ESC
-
+
-
+
2.23274
1
(+) L1
2
Communication
8
7
6
5
Display
4-20mA
4-
+3
N
4 … 20 mA
passive
1)
To the indicating instrument in the
sensor cover or to the external indicat-
ing instrument VEGADIS 50
Power supply
4 … 20 mA
active
M20 x 1.5
(diameter of the
connection cable
5 … 9 mm)
M20 x 1.5
(diameter of
the connec-
tion cable
6 … 9 mm)
M20 x 1.5
To the indicating
instrument in the
sensor cover or to
the external
indicating instru-
ment VEGADIS 50
Sockets for connec-
tion of VEGACON-
NECT 2
(communication
sockets)
1)
4 … 20 mA passive means that the sensor
consumes a level dependent current of
4 … 20 mA (consumer).