Terminal assignment, Technical specifications, Functional description – Bosch FPP-5000-TI Trouble Interface for FPP-5000 User Manual
Page 13: Terminal assignment technical specifications

FPP-5000-TI
en
13
Bosch Sicherheitssysteme GmbH
F.01U.081.396 | 3.0 | 2009.07
Functional Description
The FPP-5000-TI is an extension for the FPP-5000 External Power Supply Unit Kit 24 V/6 A.
It provides the fault message transfer of the mains fault signal and the battery fault signal to
the fire panel via the Local SecurityNetwork LSN. The two fault messages are provided by the
corresponding outputs at the BCM-0000-B Battery Controller Module. The FPP-5000-TI is
directly connected to the LSN data bus and is also power supplied via the LSN data bus line.
Terminal Assignment
Technical Specifications
Pos.
Labelling
Connection
1
AUX1 -
Auxiliary power supply incoming
(support points to loop through)
2
AUX1 +
3
LSN1 a1 -
LSN incoming
4
LSN1 b1 +
5
SHIELD
Shield wire
6
SHIELD
7
AUX2 -
Auxiliary power supply outgoing
(support points to loop through)
8
AUX2 +
9
LSN1 a2 -
LSN outgoing
10
LSN1 b2 +
11
AC FAULT -
Mains fault input
12
AC FAULT +
13
BATT FAULT -
Battery fault input
14
BATT FAULT +
FPP-5000-TI Trouble Interface for FPP-5000
Input voltage (min - max)
+15 V DC. . . +33 V DC
Maximum current consumption
1.15 mA at 24 V DC (from LSN)
Protection type as per IEC 60529 IP 20
Permissible operating temp.
-5 °C . . . 50 °C (23 °F . . . 122 °F)
Permissible storage temp.
-20 °C . . . 60 °C (-4 °F . . . 140 °F)
Relative humidity
Max. 95 % non-condensing
Address setting
Via eight DIP switches
Housing material and color
ABS plastic, (UL94 V-0), semi-gloss anthracite, RAL 7016
Dimensions (W x H x L)
Approx. 127 x 96 x 60 mm (approx. 5.0 x 3.8 x 2.4 inches)