Notes, Functions, Address setting – Bosch FLM-420-EOL4W EOL Module LSN User Manual
Page 12: Connection, Technical data, Connection technical data

12
en
FLM-420-EOL4W-D | FLM-420-EOL4W-S
F.01U.121.916 | 5.0 | 2011.05
Bosch Sicherheitssysteme GmbH
Notes
Functions
The FLM-420-EOL4W EOL Module LSN can detect faults in the LSN line and auxiliary power in
accordance with EN 54-13, and uses the line to report an error on the fire panel's operating
panel.
The FLM-420-EOL4W is used to complete LSN loops and LSN stubs. Please use the FLM-420-
EOL2W EOL module to terminate LSN T-taps.
Address setting
Use a slotted-head screwdriver to move the rotary switches to the required position.
Connection
Technical data
-
Installation must only be performed by authorized and specialized personnel!
-
Every end of the LSN bus at which 4-wire elements are connected must be terminated
with an EOL module.
-
Country-specific standards and guidelines must be observed during installation.
-
If loop wiring is present, the power supply must only terminate in the loop when ERT is
used. If no ERT system is present, the power supply must terminate at the FLM-420-
EOL4W module.
NOTICE!
The FLM-420-EOL4W cannot be used to terminate T-taps.
Description
Function
LSN a1-
LSN in
LSN b1+
LSN a2-
LSN outgoing
LSN b2+
POW IN +U
Power supply, incoming
POW IN 0V
POW OUT +U
Power supply, outgoing (only required with ERT system)
POW OUT 0V
Shield
Cable shielding
8¸M888N
HGO8AF
88
88¸M888N
HGO8GML
DKF
Z¦88[¸8888Z¦88[¸88888Kab^e]
FLM-420-EOL4W-D
FLM-420-EOL4W-S
AUX input voltage
8 VDC to 30 VDC
LSN input voltage
15 VDC to 33 VDC
AUX current consumption
< 5.0 mA
LSN current consumption
< 2.0 mA
Housing material
ABS + PC blend
Housing color
Signal white (RAL 9003)
Dimensions
Approx. 77 x 86 x 44 mm
Approx. 126 x 126 x 71 mm
Weight
85 g
346 g
Permitted operating temperature
-20 °C to +55 °C
Permitted storage temperature
-25 °C to +85 °C
Permitted relative humidity
<96%, non-condensing
Protection class compliant with IEC 60529
IP 30
IP 54