Notes

Functions

The FLM-420-EOL4W EOL Module LSN can detect faults in the LSN line and auxiliary power in
accordance with EN 54-13, and uses the line to report an error on the fire panel's operating
panel.
The FLM-420-EOL4W is used to complete LSN loops and LSN stubs. Please use the FLM-420-
EOL2W EOL module to terminate LSN T-taps.

Address setting

Use a slotted-head screwdriver to move the rotary switches to the required position.

Connection

Technical data

-

Installation must only be performed by authorized and specialized personnel!

-

Every end of the LSN bus at which 4-wire elements are connected must be terminated
with an EOL module.

-

Country-specific standards and guidelines must be observed during installation.

-

If loop wiring is present, the power supply must only terminate in the loop when ERT is
used. If no ERT system is present, the power supply must terminate at the FLM-420-
EOL4W module.

NOTICE!

The FLM-420-EOL4W cannot be used to terminate T-taps.

Description

Function

LSN a1-

LSN in

LSN b1+
LSN a2-

LSN outgoing

LSN b2+
POW IN +U

Power supply, incoming

POW IN 0V
POW OUT +U

Power supply, outgoing (only required with ERT system)

POW OUT 0V
Shield

Cable shielding

8¸M888ˆN
HGO8AF

88

88¸M888ˆN
HGO8GML

DKF

Z¦88[¸8888Z€¦88[€¸88888Kab^e]

FLM-420-EOL4W-D

FLM-420-EOL4W-S

AUX input voltage

8 VDC to 30 VDC

LSN input voltage

15 VDC to 33 VDC

AUX current consumption

< 5.0 mA

LSN current consumption

< 2.0 mA

Housing material

ABS + PC blend

Housing color

Signal white (RAL 9003)

Dimensions

Approx. 77 x 86 x 44 mm

Approx. 126 x 126 x 71 mm

Weight

85 g

346 g

Permitted operating temperature

-20 °C to +55 °C

Permitted storage temperature

-25 °C to +85 °C

Permitted relative humidity

<96%, non-condensing

Protection class compliant with IEC 60529

IP 30

IP 54