beautypg.com

Safety notes, Functional description, Address setting – Bosch FLM-420-RLV8-S Octo-relay Interface Module Low Voltage User Manual

Page 11: Connection, Technical specifications, On guide

background image

FLM-420-RLV8-S

en

11

Bosch Sicherheitssysteme GmbH

F.01U.032.851 | 5.0 | 2011.12

Safety Notes

Functional description

The FLM-420-RLV8-S Octo-relay Interface Module Low Voltage has eight change-over contact relays to provide a
potential free output contact.
The programming is carried out via the programming software of the fire panel.
Cables are fed through rubber bushings or PG cable glands (see Figure 3, Page 5).
The pluggable terminal blocks of the interface module allow for an easy wiring (even if built in).

Address setting

Fit a rotary switch in the required position using a pan head slotted screwdriver (see Figure 4, Page 6).

Connection

See Figure 6, Page 7.

Technical specifications

NOTICE!

Installation must only be performed by authorized and specialized personnel!

CAUTION!

Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.

Address (A)

Operating mode

0 0 0

Loop/stub in LSN improved version mode with automatic addressing

0 0 1 - 2 5 4

Loop/stub/T-taps in LSN improved version mode with manual addressing

CL 0 0

Loop/stub in LSN classic mode (address range: max. 127)

2 5 5 - 2 9 9

Non-permitted address range (error message on fire panel)!

Description

Function

+U | 0V

Auxiliary power supply (support points to loop through)

LSN

a1- | b1+

LSN incoming

LSN

Shield

Cable shielding (if present)

+U | 0V

Auxiliary power supply (support points to loop through)

LSN

a2- | b2+

LSN outgoing

REL1 - REL8

NC | COM | NO

Relay 1 to relay 8 (NC contact/COM/NO contact)

8 relays (low voltage)

NC contact/COM/NO contact

LSN input voltage

15 to 33 V DC

Max. current consumption from LSN

3,55 mA

Contact load (resistive load)
-

Max. switched current and voltage

2 A / 30 V DC; 0.5 A / 42.4 V AC

-

Min. switched current and voltage

0.01 mA / 10 mV DC; 0.01 mA / 10 mV AC

-

Max. AC frequency

100 Hz

Permissible wire diameter

0.6 to 3.3 mm

2

Permissible operating temperature

-20 °C to +65 °C

Permissible storage temperature

-25 °C to +80 °C

Permissible rel. humidity

<96 %, non-condensing

Protection class as per IEC 60529

IP 54

Classes of equipment as per IEC 60950

Class III equipment

Housing material and color

ABS+PC-FR, signal white (RAL 9003)

Dimensions (W x H x D)

Approx. 140 mm x 200 mm x 48 mm