Safety notes, Functional description, Address setting – Bosch FLM-420-RLV8-S Octo-relay Interface Module Low Voltage User Manual
Page 11: Connection, Technical specifications, On guide

FLM-420-RLV8-S
en
11
Bosch Sicherheitssysteme GmbH
F.01U.032.851 | 5.0 | 2011.12
Safety Notes
Functional description
The FLM-420-RLV8-S Octo-relay Interface Module Low Voltage has eight change-over contact relays to provide a
potential free output contact.
The programming is carried out via the programming software of the fire panel.
Cables are fed through rubber bushings or PG cable glands (see Figure 3, Page 5).
The pluggable terminal blocks of the interface module allow for an easy wiring (even if built in).
Address setting
Fit a rotary switch in the required position using a pan head slotted screwdriver (see Figure 4, Page 6).
Connection
Technical specifications
NOTICE!
Installation must only be performed by authorized and specialized personnel!
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing
0 0 1 - 2 5 4
Loop/stub/T-taps in LSN improved version mode with manual addressing
CL 0 0
Loop/stub in LSN classic mode (address range: max. 127)
2 5 5 - 2 9 9
Non-permitted address range (error message on fire panel)!
Description
Function
+U | 0V
Auxiliary power supply (support points to loop through)
LSN
a1- | b1+
LSN incoming
LSN
Shield
Cable shielding (if present)
+U | 0V
Auxiliary power supply (support points to loop through)
LSN
a2- | b2+
LSN outgoing
REL1 - REL8
NC | COM | NO
Relay 1 to relay 8 (NC contact/COM/NO contact)
8 relays (low voltage)
NC contact/COM/NO contact
LSN input voltage
15 to 33 V DC
Max. current consumption from LSN
3,55 mA
Contact load (resistive load)
-
Max. switched current and voltage
2 A / 30 V DC; 0.5 A / 42.4 V AC
-
Min. switched current and voltage
0.01 mA / 10 mV DC; 0.01 mA / 10 mV AC
-
Max. AC frequency
100 Hz
Permissible wire diameter
0.6 to 3.3 mm
2
Permissible operating temperature
-20 °C to +65 °C
Permissible storage temperature
-25 °C to +80 °C
Permissible rel. humidity
<96 %, non-condensing
Protection class as per IEC 60529
IP 54
Classes of equipment as per IEC 60950
Class III equipment
Housing material and color
ABS+PC-FR, signal white (RAL 9003)
Dimensions (W x H x D)
Approx. 140 mm x 200 mm x 48 mm