POWER
IN OUT I
PI+ | PI-
Power supply output 1 to 4
OUT I
PI+ | 4- to PI+ | 1-
Reference potential (PI+), switched negative potential output 1 to 4
OUT II
PII+ | 8- to PII+ | 5-
Reference potential (PI+), switched negative potential output 5 to 8
POWER
IN OUT II
PII+ | PII-
Power supply output 5 to 8
LSN input voltage
15 to 33 V DC
Max. current consumption from LSN
5,5 mA
Outputs
8, independent
-
Max. switched voltage of outputs
30 V DC
-
Max. output current rating
700 mA per output (depending on external power supply)
-
External power supply
5 to 30 V DC
Inputs
2, independent
1. Line monitoring with EOL:
-
EOL resistor
Nominal 3,9 k
Ω
-
Overall line resistance R
Σ
(R
Σ
= R
L/2
+ R
L/2
+ R
EOL
)
-
In standby: 1500
Ω - 6000 Ω
-
Short-circuit: < 800
Ω
-
Interruption: > 12000
Ω
2. Contact monitoring:
-
Max. current strength (current pulse)
8 mA
Minimum activation time of the inputs IN 1 - 2
3,2 s
Maximum cable length of all inputs and outputs
which are connected to the loop or stub and not
electrically isolated from LSN
500 m in total
Permissible wire diameter
0.6 to 3.3 mm
2
Permissible operating temperature
-20 °C to +65 °C
Permissible storage temperature
-25 °C to +80 °C
Permissible rel. humidity
<96 %, non-condensing
Protection class as per IEC 60529
IP 54
Classes of equipment as per IEC 60950
Class III equipment
Housing material and color
ABS+PC-FR, signal white (RAL 9003)
Dimensions (W x H x D)
Approx. 140 mm x 200 mm x 48 mm
Description