Notes

Functions

The FLM-320-EOL4W-S is used to terminate conventional stubs. It can detect faults on the
conventional line and auxiliary voltage in accordance with EN 54-13, and uses the line to
report an error on the fire panel's operating panel.

Connection

Connect the EOL module as the last element in a conventional line. Set the resistance (R), the
voltage (V), and the power (P) for the line via the DIP switches, using the FSP-5000-RPS
programming software to calculate the values and the associated DIP settings.

Technical data

-

Installation must only be performed by authorized and specialized personnel!

-

An EOL module must be connected at the end of every conventional line.

-

Country-specific standards and guidelines must be observed during installation.

-

You are required to use the FSP-5000-RPS programming software for the FPA-5000 fire
panel to calculate which programming is required via the DIP switches.

Description

Function

CONV b+

Conventional line, incoming

CONV a-

POWER +U

Power supply

POWER 0V

Shield

Cable shielding

POWER CONV
Shield +U 0V b+ a-

R

V

P

AUX input voltage

8 VDC to 30 VDC

Conventional input voltage

9 VDC to 30 VDC

AUX current consumption

< 5.5 mA

Conventional current consumption

< 2.0 mA

Housing material

ABS + PC blend

Housing color

Signal white, RAL 9003

Dimensions (H x W x D)

Approx. 126 x 126 x 71 mm

Weight

342 g

Permitted operating temperature

-20 °C to 55 °C

Permitted storage temperature

-25 °C to 85 °C

Permitted relative humidity

<96%, non-condensing

Protection class compliant with IEC 60529