7800 SERIES RELAY MODULES

65-0229—1

Table 3. Hold and Fault Message Summary.

Fault Code

System Failure

Recommended Troubleshooting

Fault 1

*No Purge Card*

No card is plugged into the
purge card slot.

1.

Make sure the purge card is seated properly.

2.

Inspect the purge card and connector on the relay module for

damage or contaminants.

3.

Reset and sequence the relay module.

4.

If the fault code reappears, replace the purge card.

5.

Reset and sequence the relay module.

6.

If the fault persists, replace the relay module.

Fault 2

*AC Frequen/Noise*

Excess noise or device
running on slow ac.

1.

Check the relay module and display module connections.

2.

Reset and sequence the relay module.

Fault 3

*AC Line Dropout*

Ac line dropout detected.

3.

Check the relay module power supply and make sure that both

frequency and voltage meet the specifications.

Fault 4

*AC Frequency*

Device running on fast ac.

4.

Check the backup power supply, as appropriate.

Fault 5

*Low Line Voltage*

Low ac line detected.

Fault 6

*Purge Card Error*

Purge card timing changed
since card was initially read.

1.

Make sure the purge card is seated properly.

2.

Inspect the purge card and connector on the relay module for

damage or contaminants.

3.

Reset and sequence the relay module.

4.

If the fault code reappears, replace the purge card.

5.

Reset and sequence the relay module.

6.

If the fault persists, replace the relay module.

Fault 7

*Flame Amplifier*

Flame sensed when flame
not present.

1.

Check wiring and correct any errors. Make sure that flame

sensor wires are in separate conduits. Check for noise
coupling into the flame detector leadwires.

2.

Make sure that flame detector and flame amplifier are

compatible.

3.

Remove the flame amplifier and inspect connections. Reseat

the amplifier.

4.

Reset and sequence the relay module.

5.

If the code reappears, replace the amplifier and/or the flame

detector.

Fault 8

*Flame Amp/Shutr*

Flame sensed when no
signal expected during
shutter-check or Ampli-
Check™ versions.

6.

If the fault persists, replace the relay module.

Fault 9

*Flame Detected*

Flame sensed when shutter
open and no flame is
expected during STANDBY.

1.

Check that flame is not present in the combustion chamber;

correct any errors.

2.

Check wiring and correct any errors. Make sure that flame

sensor wires are in separate conduits. Check for noise
coupling into flame detector leadwires.

3.

Remove the flame amplifier and inspect its connections.

Reseat the amplifier.

4.

Reset and sequence the relay module.

5.

If the code reappears, replace the amplifier and/or the flame

detector.

6.

If the fault persists, replace the relay module.

Fault 10

*Preignition ILK*

Preignition Interlock fault
during STANDBY
*EC/RM7800, 7840, 7838B
only).

1.

Check wiring and correct any errors.

2.

Check Preignition Interlock switches to assure proper

functioning.

3.

Check fuel valve operation.

4.

Reset and sequence the relay module; monitor the Preignition

Interlock status.

5.

If the code persists, replace the relay module.

(continued)