Grounding series-stacked inverters, To ground series-stacked inverters, Grounding series-stacked inverters –3 – Xantrex Technology power Inverter Stacking User Manual
Page 21: Figure 2-2, Dc grounding of series-stacked inverters –3
DC Wiring
975-0059-01-01 Rev A
2–3
Grounding Series-stacked Inverters
To ground series-stacked inverters:
1.
Connect the ground bond in the DC disconnect between the inverters and the
batteries to the primary grounding electrode, in accordance with local and
national electrical codes.
2.
Connect an appropriately sized ground wire from the chassis bonding ground
lug on the L1 inverter DC end to the ground bond inside the DC disconnect.
3.
Connect a second appropriately sized ground wire from the chassis bonding
ground lug on the L2 inverter DC end to a different terminal in the ground
bond inside the DC disconnect.
Figure 2-2 DC Grounding of Series-stacked Inverters
GROUND
SHUNT &
NEGATIVE BUS
DC
DISCONNECT
01A Inverter
OFF SRCH ON CHG
R e s e t D e fa u lts
C o n tr a s t
O N /O F F
M E N U
M E N U
HE A D IN G S
M E N U
IT E M S
S E T
P O IN T S
INV
GEN
I nver t er Cont r ol M odul e
G R ID T IE
IN V ER T
A C 2
F L O A T
S T A T U S
E R R O R
B U L K
A C 1
xantrex
+
–
xantrex
S i ne Wave P l us I nverter/ Charger
Chassis Bonding
Ground Lug
L1 Inverter
01A Inverter
OFF SRCH ON CHG
R e s e t D e fa u lts
C o n tr a s t
O N /O F F
M E N U
M E N U
H E A D IN G S
M E N U
IT E M S
S E T
P O IN T S
INV
GEN
I nver t er Cont r ol M odule
G R ID T IE
IN V ER T
A C 2
F L O A T S T A T U S
E R R O R
B U L K
A C 1
xantrex
+
–
xantrex
S i ne Wave P l us Inverter/ Charger
L2 Inverter
To primary
Earth/ground
connections
ON
OFF
ON
OFF
ON
OFF
Chassis Bonding
Ground Lug