beautypg.com

York PT9 User Manual

Page 3

background image

036-21581-001 Rev. C (0205)

Unitary Products Group

3

* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.

NOTES:

1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
4. All filters must be high velocity cleanable type.
5. Air flows above 1800 CFM require either return from two sides or one side plus bottom.

ELECTRICAL AND PERFORMANCE DATA

Models

Input High/Low

Output High/

Low

Blower Size

Blower

Max.

Over-current

Protect

Air Temp. Rise

MBH

MBH

In.

HP

Amps

°F

PT9A12N040UP11

40/26

38/24

11 x 8

1/2

7.7

20

35 - 65

PT9B12N060UP11

60/39

56/36

11 x 8

1/2

7.7

20

40 - 70

PT9B12N080UP11

80/52

75/49

11 x 8

1/2

7.7

20

45 - 75

PT9C16N080UP11

80/52

75/49

11 x 10

3/4

10.2

20

45 - 75

PT9C16N100UP11

100/65

93/60

11 x 10

3/4

10.2

20

45 - 75

PT9C20N100UP11

100/65

93/60

11 x 11

1

12.8

20

45 - 75

PT9D20N120UP11

120/78

112/73

11 x 11

1

12.8

20

40 - 70

Models

Max. Outlet

Air Temp.

Nominal

Airflow

Cabinet Width

Total Unit

AFUE

Min. Wire Size

(awg) @ 75 ft.

One Way

Approximate

Operating Weight

°F

CFM

In.

Amps

%

PT9A12N040UP11

165

1200

14-1/2

9

94.0

14

121

PT9B12N060UP11

170

1200

17-1/2

9

93.2

14

135

PT9B12N080UP11

175

1200

17-1/2

9

92.5

14

142

PT9C16N080UP11

175

1600

21

12

92.8

14

157

PT9C16N100UP11

175

1600

21

12

92.5

14

162

PT9C20N100UP11

175

2000

21

14

92.8

12

164

PT9D20N120UP11

170

2000

24-1/2

14

93.2

12

180

BLK

WHT

GRN

BLK (HOT)

WHT (NEUTRAL)

GRN

NOMINAL
120 VOLT

LINE WIRING CONNECTIONS

SINGLE STAGE HEATING

THERMOSTAT CONNECTIONS

SINGLE STAGE HEATING AND TWO-STAGE COOLING

THERMOSTAT CONNECTIONS

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W

G

Y1

C

R

G

C
COMMON T’STAT CONNECTION

Y2

Y1

W1/W

Y/Y2

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W

G

Y
C

R

G

C

COMMON T’STAT CONNECTION

W1/W

Y/Y2

ROOM
THERMOSTAT

FURNACE
CONTROL

CONDENSING
UNIT

TO AIR CONDITIONER
CONTROLS

R

W1
W2

G

Y2

R

G

COMMON T’STAT CONNECTION

Y1

Y1

W1/W

C

C

W2

Y/Y2

TWO-STAGE HEATING AND TWO-STAGE COOLING

THERMOSTAT CONNECTIONS