Technical information, Page 124 – Xantrex Technology SW Series User Manual
Page 132
TECHNICAL INFORMATION
Page
124
2001 Xantrex Technology, Inc.
5916 - 195th Street N. E.
Arlington, WA 98223
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
SW Series Inverter/Charger
Part No. 2031-5
Rev. C: February 2001
SETUP MENU – 12 VDC (120 VAC/60HZ) MODELS
To access the SETUP MENU, press the RED and GREEN buttons on your CONTROL PANEL (or
SWRC) at the same time. To exit the Setup Menu, press the ON/OFF MENU button or use the down
MENU HEADING button until you reach the USER MENU (menu headings 1 – 8)
.
MENU HEADING
MENU ITEM
SELECTION
RANGE
DEFAULT
SETTINGS
USER
SETTINGS
Inverter Setup
9
Set Grid Usage
FLT SELL SLT LBX
FLT
Set Low Battery cut out VDC
0.80 – 25.5
11.0
Set LBCO delay minutes
00 - 255
15
Set Low battery cut in VDC
00.0 – 16.5
13.0
Set High battery Cut Out VDC
00.0 – 16.5
16.0
Set search watts
00 - 240
48
Set search spacing
00 – 255
59
Battery Charging
10
Set Bulk volts DC
10.0 – 16.0
14.4
Set Absorption time h:m
00:00 – 23:50
02:00
Set Float volts DC
10.0 – 16.0
13.4
Set Equalize volts DC
10.0 – 16.0
14.4
Set Equalize time h:m
00:00 – 23:50
02:00
Set Max Charge amps AC
01 - 25
20
Set Temp Comp
LeadAcid Nicad
LeadAcid
AC Inputs
11
Set Grid (AC1) amps AC
00 - 63
60
Set Gen (AC2) amps AC
00 - 63
30
Set Input lower limit VAC
80 - 111
108
Set Input upper limit VAC
128 - 149
132
Gen Auto Start Setup
12
Set Load Start amps AC
00 - 63
33
Set Load Start delay min
00.0 – 25.5
05.0
Set Load Stop delay min
00.0 – 25.5
05.0
Set 24 hr start volts DC
05.0 – 25.5
12.3
Set 2 hr start volts DC
05.0 – 16.5
11.8
Set 15 min start volts DC
05.0 – 16.5
11.3
Read LBCO 30 sec start VDC
05.0 – 16.5
11.0
Set Exercise period days
00 - 255
30
Set Maximum run time h:m
00:00 – 23:50
08:00
Gen Starting Details
13
Set RY7 Function
GlowStop Run
Run
Set Gen warmup seconds
16 - 255
60
Set Pre Crank seconds
00 - 255
10
Set Max Cranking seconds
01 - 15
10
Set Post Crank seconds
00 - 255
30
Auxiliary Relays R9 R10
14
Set Relay 9 volts DC
00.0 – 16.5
14.5
R9 Hysteresis volts DC
00.1 – 12.8
01.0
Set Relay 10 volts DC
00.0 – 16.5
14.8
R10 Hysteresis volts DC
00.1 – 12.8
01.0
Set Relay 11 volts DC
00.0 – 16.5
15.0
R11 Hysteresis volts DC
00.1 – 12.8
01.0
Bulk Charge Trigger Timer
15
Start Bulk Time H:M
00:00 – 23:50
00:00
Low Battery Transfer (LBX) 16
Set Low Battery transfer VDC
05.0 – 16.5
11.3
Set Low Battery cut in VDC
05.0 – 16.5
13.0
Battery Selling
17
Set Battery Sell volts DC
10.0 – 16.0
13.4
Set Max Sell amps AC
01 - 25
30
Grid Usage Timer
18
Set Start Charge time h:m
00:00 – 23:50
21:00
End Stop Charge time h:m
00:00 – 23:50
21:00