Nominal external static pressure is 0.50” w.c. at furnace outlet ahead of cooling coils.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
NOTES:
1. For altitudes above 2000 ft. reduce capacity 4% for each 1000 ft. above sea level.
2. Wire size based on copper conductors, 60°C, 3% voltage drop.
3. Continuous return air temperature must not be below 55°F.
ELECTRICAL AND PERFORMANCE DATA
Model
Input/
Cabinet
Output
Nominal
Airflow
Cabinet
Width
Total Unit
AFUE
Air Temp. Rise
MBH
MBH
CFM
In.
Amps
%
°F
GY9S040A12UP11
40/A
38
1200
14-1/2
9
94.0
35 - 65
GY9S060B12UP11
60/B
56
1200
17-1/2
9
92.0
40 - 70
GY9S080B12UP11
80/B
74
1200
17-1/2
9
92.0
45 - 75
GY9S080C16UP11
80/C
75
1600
21
12
92.0
45 - 75
GY9S080C20UP11
80/C
75
2000
21
14
92.0
40 - 70
GY9S100C16UP11
100/C
93
1600
21
12
92.0
45 - 75
GY9S100C20UP11
100/C
93
2000
21
14
92.0
40 - 70
GY9S120D20UP11
120/D
112
2000
24-1/2
14
92.0
40 - 70
GY9S135D20UP11
135/D
127
2000
24-1/2
14
92.0
45 - 75
Model
Input/
Cabinet
Max.
Outlet
Air Temp.
Blower
Blower
Size
Max.
Over-current
Protect
Min. Wire Size
(awg) @ 75 ft.
One Way
Operating
Wt
MBH
°F
HP
Amps
In.
Lbs.
GY9S040A12UP11
40/A
165
1/2
7.0
11 x 8
20
14
119
GY9S060B12UP11
60/B
170
1/2
7.0
11 x 8
20
14
133
GY9S080B12UP11
80/B
175
1/2
7.0
11 x 8
20
14
140
GY9S080C16UP11
80/C
175
3/4
10.2
11 x 10
20
14
155
GY9S080C20UP11
80/C
170
1
12.7
11 x 11
20
12
157
GY9S100C16UP11
100/C
175
3/4
10.2
11 x 10
20
14
160
GY9S100C20UP11
100/C
170
1
12.7
11 x 11
20
12
162
GY9S120D20UP11
120/D
170
1
12.7
11 x 11
20
12
178
GY9S135D20UP11
135/D
175
1
12.7
11 x 11
20
12
178