LOCKOUT BYPASS OPTION

FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY. OPERATORS SHOULD NOT USE THIS
FEATURE DUE TO POSSIBILITY OF EQUIPMENT
OR PROPERTY DAMAGE, OR PERSONAL INJURY.

COMPRESSOR SHORT TERM

CYCLE PROTECTION

This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature

while testing thermostat operation, simply press

ADV

PRGM

and

HOLD
TEMP

buttons at the same time at initial startup.

DO NOT USE THE LOCKOUT BYPASS OPTION
UNLESS THE COMPRESSOR OIL HEATERS HAVE
BEEN OPERATIONAL FOR 6 HOURS AND THE
SYSTEM HAS NOT BEEN OPERATIONAL FOR AT
LEAST 5 MINUTES.

COOLING SYSTEM

To prevent compressor and/or property damage,
if power to the compressor has been off or
interrupted for more than 1 hour and the outdoor
temperature is below 50

°

F, DO NOT operate the

system for at least the amount of time the com-
pressor was off! This will allow the compressor
heaters to warm the compressor oils to avoid
damage due to slugging.

1.

Press

SYSTEM

HEAT-OFF-COOL-AUTO

until COOL is displayed.

2.

Press

to adjust thermostat below room tem-

perature to call for cool. The blower should come on
immediately, followed by cold air circulation. How-
ever, if the red LED on the thermostat front is flashing,
the compressor lockout feature is operating (see
Lockout Bypass Option to temporarily override the
compressor lockout feature during testing).

If the thermostat display is operating properly, but the
cooling system does not operate when the above
steps are performed, the red jumper wire (provided
with thermostat) may not be properly installed be-
tween the RH and RC terminals. Disconnect electri-
cal power to system and properly install the jumper
wire per the appropriate wiring schematic.

Refer to the OPERATION GUIDE if you need additional
information on thermostat operation.

TROUBLESHOOTING

Refer to the Question & Answer section of the OPERA-
TION GUIDE
for information on troubleshooting the ther-
mostat.