2.
Manual Changeover (Heating/Cooling Systems
Only)
3.
Heat Only Systems
4.
Cool Only Systems
5.
Computed Energy Management Recovery (EMR)
— With EMR enabled, system will be energized
before the next program period begins, to achieve
programmed temperature by the beginning of the
next program period (the thermostat's microcom-
puter calculates 15 minutes for every 2
°
F tempera-
ture change). For example, assume that the thermo-
stat is programmed to provide an overnight heating
temperature of 62
°
F, and during the next program
period, programmed to begin at 6:00 AM, the pro-
grammed temperature is 70
°
F. With EMR activated,
the thermostat will automatically activate the heating
system at 5:00 AM, so that the programmed tempera-
ture of 70
°
F is reached by about 6:00 AM.
C. ELECTRIC HEAT SYSTEMS
For central electric heat systems where the blower is
energized by a separate circuit through the fan relay
(meaning that the fan turns on immediately on call for
heat), clip wire W14 on the back of the thermostat (see fig.
13). If the thermostat is energizing electric heat sequenc-
ers, DO NOT clip wire W14.
CHECK THERMOSTAT OPERATION
When checking thermostat, Group B option switches #1
and #2 for automatic changeover must be in the OFF
position. This will allow temporary setting of heat setpoints
above cool setpoints. After system checkout, reset Group
B option switch #1 to ON position if automatic changeover
is desired (see SET GROUP B OPTION SWITCHES).
FAN OPERATION
1.
Turn on power to the system. If the heat source has
a standing pilot, be sure to light it.
ON
1
2
3
Switch #1 OFF
Switch #2 OFF
Switch #3 (see step B5)
ON
1
2
3
Switch #1 OFF
Switch #2 ON
Switch #3 (see step B5)
ON
1
2
3
Switch #1 ON
Switch #2 ON
Switch #3 (see step B5)
2.
Press
FAN
ON – AUTO
until FAN ON is displayed. The blower
should begin to operate (this will work only on sys-
tems with a G terminal).
On three-wire heat only systems, or on four-wire heat/
cool systems, if the thermostat display is operating
properly, but the fan does not operate when
FAN
ON – AUTO
is pressed, the red jumper wire (provided with thermo-
stat) may not be properly installed between the RH
and RC terminals. Disconnect electrical power to
system and properly install the jumper wire per the
appropriate wiring diagram.
3.
Press
FAN
ON – AUTO
until FAN AUTO is displayed. The
blower should stop operating within approximately
one minute.
HEATING SYSTEM
1.
Press
SYSTEM
HEAT-OFF-COOL-AUTO
until HEAT is displayed (it may already
be displayed).
2.
Press
to adjust thermostat above room tem-
perature to call for heat. The heating system should
begin to operate.
ON
1
2
3
Switch #1 (see steps B1–B4)
Switch #2 (see steps B1–B4)
Switch #3 OFF
NOTE
LOCKOUT BYPASS OPTION
FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY. OPERATORS SHOULD NOT USE THIS
FEATURE DUE TO POSSIBILITY OF EQUIPMENT
OR PROPERTY DAMAGE, OR PERSONAL INJURY.
COMPRESSOR SHORT TERM
CYCLE PROTECTION
This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature
while testing thermostat operation, simply press
ADV
PRGM
and
HOLD
TEMP
buttons at the same time at initial startup.
DO NOT USE THE LOCKOUT BYPASS OPTION
UNLESS THE COMPRESSOR OIL HEATERS HAVE
BEEN OPERATIONAL FOR 6 HOURS AND THE
SYSTEM HAS NOT BEEN OPERATIONAL FOR AT
LEAST 5 MINUTES.