Downdraft Ventilation System

INSTALLATION WITH COOKTOP

NOTE: To install a downdraft with a Wolf cooktop, you must
allow for a minimum 25

1

/

8

"

(638)

flat counter space from front to

back. A countertop with a raised lip or backsplash may not
allow enough space for proper installation.

Location of the electrical outlet must be within reach of the
power cord which is located midway, top and bottom, on the
right side of the downdraft. Unless oversized cabinets are used,
the outlet cannot be located on the back wall of the cabinet, but
may be placed in adjacent cabinetry.

25

1/8

"

(638) min

FLAT COUNTERTOP

7

11/16

"

(197)

24"

min (610)

CABINET DEPTH

2

1/2

"

(64) min

EDGE OF

COOKTOP

TO WALL

7

1/8

"

(181)

2

1/2

"

(64) min

2

3/4

"

(70)

COOKTOP CUT-OUT

WIDTH

19

1/4

"

(489)

27"

(686),

33"

(838) OR

42"

(1067)

DOWNDRAFT CUT-OUT

25

1/8

"

(638) min

FLAT

COUNTERTOP

3"

(76) min

TO CONTROL

MODULE

COUNTERTOP CUT-OUT (TOP VIEW)

29

5/16

"

(745)

SIDE VIEW

30"

(762) rec

FLAT COUNTERTOP

29

5/16

"

(745)

7

1/2

"

(191)

27

1/4

"

(692) min

CABINET DEPTH

7

1/8

"

(181)

27"

(686) OR

33"

(838)

DOWNDRAFT CUT-OUT

2

3/4

"

(70)

30"

(762) OR

36"

(914)

WIDTH OF RANGETOP

30"

(762) rec
FLAT

COUNTERTOP

24"

(610) min*

COUNTERTOP CUT-OUT (TOP VIEW)

3"

(76) min

TO CONTROL

MODULE

19"

(483)

PLATFORM DEPTH

2

1/2

"

(64) min

EDGE OF

RANGETOP

TO WALL

*Additional depth may be required if rangetop is to be installed flush with cabinet face.

SIDE VIEW

INSTALLATION WITH SEALED BURNER RANGETOP

Installation of the remote-mounted control module must be
within 10'

(3 m)

of the downdraft assembly and a minimum of

4"

(102)

from the outer edge of cooktop element or burner.

This manual is related to the following products: