beautypg.com

Troubleshooting chart, Flame lock, Safety system operational checklist – Whirlpool Residential Gas Water Heater with the Flame Lock Safety System User Manual

Page 26

background image

26

Removing and Replacing the Gas
Control Valve/Thermostat

IMPORTANT: The gas control valve/thermostat is a standard

valve with wire leads that connect to a thermal switch.
Removing the Gas Control Valve/Thermostat:
1. Turn the gas control/temperature knob to the “OFF”

position (Figure 19A).

2. Turn off the gas at the manual shut-off valve on the gas

supply pipe (Figure 3).

3. Drain the water heater. Refer to the section of “Draining

and Flushing” and follow the procedure.

4. Disconnect the igniter wire from the igniter lead wire. Use

needle nose pliers to disconnect the red (+) and white (-)

thermopile wires. Disconnect pilot tube (7/16” wrench)

and manifold tube (3/4” wrench) at the gas control valve/

thermostat (Figure 22). NOTE: L.P. Gas systems use

reverse (left-hand) threads on the manifold tube.

5. Refer to “Gas Piping” (Figure 3) and disconnect the

ground joint union in the gas piping. Disconnect the

remaining pipe from the gas control valve/thermostat.

6. To remove the gas control valve/thermostat, thread a 4”

section of gas pipe into the inlet and use it to turn the

Flame Lock

®

Safety System Operational Checklist

TROUBLESHOOTING CHART

gas control valve/thermostat (counterclockwise.) Do not

use pipe wrench or equivalent to grip body. Damage

may result, causing leaks. Do not insert any sharp

objects into the inlet or outlet connections. Damage to

the gas control valve/thermostat may result.

Gas Control Valve/Thermostat:
To replace the gas control valve/thermostat, reassemble

in reverse order. When replacing the gas control valve/

thermostat, thread a 4” section of gas pipe into the inlet and

use it to turn the gas control valve/thermostat (clockwise.)

DO NOT OVER TIGHTEN, damage may result.

Be sure to use approved Teflon® tape or pipe joint

compound on the gas piping connections and fitting on

the back of the gas control valve that screws into tank.

Be sure to remove the pilot ferrule nut from the new gas

control valve/thermostat.

Turn the gas supply on and check for leaks. Test the

water heater by brushing on an approved noncorrosive

leak detection solution. Bubbles forming indicate a leak.

Correct any leak found.

Be sure tank is completely filled with water before

lighting and activating the water heater. Follow the

“Lighting Instructions” on page 17.

If additional information is required, contact the Service

Department at: 1-877-817-6750.

5. No leaks at pilot and manifold connection.
6. Manifold door screws securely tightened.
7. Depress the button on the thermal switch.

1. Manifold gasket properly sealed.
2. Viewport not damaged or cracked.
3. Flame-trap free of debris and undamaged.
4. Manifold component block properly installed.

PROBLEM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

BURNER WILL NOT IGNITE

1. Pilot not lit

2. Thermostat set too low

3. No

gas

4. Dirt in the gas lines

5. Pilot line clogged

6. Main burner line clogged

7. Non-functioning

thermopile

8. Non-functioning

thermostat

9. Heater installed in a confined area

1. Light

pilot

2. Turn temp. dial to desired temperature

3. Check with gas utility company

4. Notify utility-install trap in gas line

5. Clean, locate source and correct

6. Clean, locate source and correct

7. Replace

thermopile

8. Replace

thermostat

9. Provide fresh air ventilation

SMELLY WATER

1. Sulfides in the water

1. Replace the anode with a special anode

BURNER FLAME YELLOW-

LAZY

1. Insufficient secondary air

2. Low gas pressure

3. Flue

clogged

4. Main burner line clogged

5. Heater installed in a confined area

6. Obstruction in main burner orifice

1. Provide ventilation to water heater

2. Check with gas utility company

3. Clean, locate source and correct

4. Clean, locate source and correct

5. Proper fresh air ventilation

6. Clean or replace orifice

PILOT WILL NOT LIGHT OR

REMAIN LIT

1. Non-functioning

igniter

2. The thermal switch tripped

3. Thermopile connection loose

4. Air in gas line

5. Proper Lighting Sequence not followed.

Gas Control / Temperature Knob was not

held in for sufficient time.

6. Low gas pressure

7. No

gas

8. Dirt in gas lines

9. Cold

drafts

10. Thermostat ECO switch open

1. Replace igniter pilot assembly

2. See Pilot Light Troubleshooting Flowchart

section

3. Seat connector firmly in socket

4. Bleed the air from the gas line

5. Do not attempt to relight if the red light is lit

and the pilot flame is not visible through the

view port. Wait until the red light is no longer

lit, then follow lighting instructions on the water

heater.

6. Check with gas utility company

7. Check with gas utility company

8. Notify utility-install dirt trap in gas line

9. Locate source and correct

10. Replace thermostat