NOTE

NOTE

The following wiring diagrams show typical terminal identifica-
tion and wiring. For proper installation, refer to the original
manufacturer’s instructions.

Relay contacts shown are thermostatically operated.

C*

R

Y2

O

B

Energized

in HEAT

Compressor

Contactor

Stage 1

Heat

Relay

Stage 1

Heat

Relay

Stage 2

Thermostat

Control

Circuit

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

Y

W

W2

Figure 3. Typical wiring diagram for single transformer systems

Fan

Relay

G

TRANSFORMER

Compressor

Contactor

Stage 2

Energized

in COOL

* The 24 Volt neutral connection

to terminal C on the thermostat
is not required if you replace
the batteries once a year with
fresh “AA” Energizer

®

alkaline

batteries.

C*

R

Y2

Compressor

Contactor

Stage 1

Heat

Relay

Stage 1

Heat

Relay

Stage 2

Thermostat

Control

Circuit

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

Y

W

W2

Figure 4. Typical wiring diagram for two-transformer systems with NO safety circuits

Fan

Relay

G

TRANSFORMER

Compressor

Contactor

Stage 2

24 VAC

120 VAC

Hot

Neutral

TRANSFORMER

TWO COMMONS MUST

BE JUMPERED TOGETHER!

CUT AND

TAPE OFF!

* The 24 Volt neutral connection

to terminal C on the thermostat
is not required if you replace
the batteries once a year with
fresh “AA” Energizer

®

alkaline

batteries.

O

Energized

in COOL

B

Energized

in HEAT

C*

R

Y2

Compressor

Contactor

Stage 1

Heat

Relay

Stage 1

Heat

Relay

Stage 2

Thermostat

Control

Circuit

Limit or

Safety

Switches

Limit or

Safety

Switches

Limit or

Safety

Switches

Limit or

Safety

Switches

24 VAC

120 VAC

Hot

Common

Common

Neutral

THERMOSTAT

SYSTEM

Y

W

W2

Figure 5. Typical wiring diagram for two-transformer systems with safety circuits in BOTH systems

Fan

Relay

G

HEATING

TRANSFORMER

Compressor

Contactor

Stage 2

24 VAC

120 VAC

Hot

Neutral

COOLING

TRANSFORMER

TWO COMMONS MUST

BE JUMPERED TOGETHER!

24 VAC

Accessory
Relay N.O.

Contact

* The 24 Volt neutral connection

to terminal C on the thermostat
is not required if you replace
the batteries once a year with
fresh “AA” Energizer

®

alkaline

batteries.

O

Energized

in COOL

B

Energized

in HEAT