WhisperKool XLT 6000 User Manual
Page 29
Page 27
XLT 112910
THIRD TEMPERATURE TEST:
10. Once the unit has run for 24 hours, perform the third temperature test.
11. Record information and calculate temperature differential in table below for the condenser/back
side section under the second test.
TEMPERATURE DATA FROM TESTING
*When measuring outlet air temperature on both sides of the unit (from the circular fans), hold the
thermostat at the outer edges of one of the circular fans.
TEMPERATURE TESTING LOCATIONS
Temperature / Test
(time)
First
(after 5 mins)
Second
(after 8 hrs)
Third
(after 24 hours)
Ev
ap
or
at
or
(F
ron
t) Side
Condenser (B
ack) Side
Inlet Air
Outlet Air
Differential
(Inlet - Outlet = _; ideally 10°F - 15°F)
Inlet Air
(Ideally < 85°F)
Outlet Air
(Ideally < 120°F)
Differential
(Inlet - Outlet = _; ideally 10°F - 15°F)
INLET AIR -- Evaporator (Front) Side*
INLET AIR -- Condenser (Back) Side*
OUTLET AIR -- Evaporator (Front) Side*
OUTLET AIR -- Condenser (Back) Side*