Installation, Selecting the blower off delay, Diagnostic features – White Rodgers 50T35-743 User Manual
Page 4
4
INSTALLATION
SELECTING THE BLOWER OFF DELAY
In the heating mode, the blower off delay can be selected
to obtain a 90, 120 or 150 seconds period. This can be
accomplished by changing the position of a plastic jumper
located on the ignition control. See the drawing below for
the location of this jumper.
The control is factory set to give a (150) second blower off
delay. See drawing below for the jumper position for all
available settings:
Notes:
•
If the jumper is removed, the control will default to a
(150) second blower off delay in the heating mode.
•
The blower on time in the heating mode is (30)
seconds and is non-adjustable.
•
The blower on time in the cooling mode is (5) seconds
and is non-adjustable.
•
The blower off delay in the cooling mode is (60)
seconds and is non-adjustable.
•
Caution is to be exercised not to bend the metal pins
when changing the time delay from the factory setting.
DIAGNOSTIC FEATURES
The 50T35-743 control continuously monitors its own
operation and the operation of the system. If a fault occurs,
the LED will indicate a fault code as shown below. If the
fault is internal to the control, the light will stay off. In
this case, the entire control should be replaced, as the
control is not field-repairable.
If the sensed failure is in the system (external to the
control), the LED will flash in the following flash-pause
sequences to indicate failure status (each flash will last
approximately 0.25 seconds, and each pause will last
approximately 2 seconds).
Monitored
LED
Condition
During
Action
Solid On
Normal
All Times
None required
1 Flash
Ignition retries
Heating
Gas Valve “Off”
exceeded
Demand
Circulator
“Delay Off”
Inducer “Off”
2 Flashes
PSW Stuck
Heating
All Outputs
Closed
Demand
“Off” except circ
Only
cool speed in
response to a
call for fan/cool
3 Flashes
PSW Stuck
Heating
All Outputs
Open
Demand
“Off” except circ
Only
cool speed in
response to a
call for fan/cool
4 Flashes
Limit Switch
Heating
Gas Valve “Off”
Open
Demand
Circulator “On”
Only
Inducer “On”
5 Flashes
Improper
All Times
Gas Valve “Off”
Flame
Circulator “On”
Inducer “On”
Rapid
Improper
Power-up Gas Valve “Off”
Flashing
Polarity
Circulator “Off”
Inducer “Off”
Twinning
All other
Gas Valve “Off”
Fault
times
Circulator “Off”
Inducer “Off”
Off
Internal error
All Times
Gas Valve “Off”
detected
Circulator “Off”
Inducer “Off”
BLOWER
TIME OFF
JUMPER
90
120
150
STATUS
TWIN
W
G
R
STATUS
90
120
150
90
120
150
90
120
150
JUMPER SET
STATUS
JUMPER SET
STATUS
JUMPER SET
FOR 90 SEC.
FOR 120 SEC.
FOR 150 SEC.