Checking gas connections, Continued – Vanguard Heating VP2000BTC User Manual
Page 16
16
103876
3. Pressurize supply piping system by either using compressed air or
opening propane supply tank valve.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and
water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
Test Pressures Equal To or Less Than 1/2 PSIG
1. Close manual shutoff valve (see Figure 15).
2. Pressurize supply piping system by either using compressed air or opening
propane supply tank valve.
3. Check all joints from propane supply tank to manual shutoff valve (see Figure
16). Apply mixture of liquid soap and water to gas joints. Bubbles forming
show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS CONNECTIONS
1. Open manual shutoff valve (see Figure 15).
2. Open propane supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from manual shutoff valve to thermostat gas valve (see Figure
16). Apply mixture of liquid soap and water to gas joints. Bubbles forming
show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, pages 17 through 19). Check all other
internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appliance, page 19).
8. Replace front panel.